1. Max. Permissible continuous operating temperature of conductor:
Silicon rubber insulation: 180℃;
Fluoroplastic insulation: 200℃;
2. The cable should be heated during installing when ambient temperature is below 0℃;
3. Allowed bending radius:
Not less than 6 times of cable outer diameter for cables without armor or screen structure;
Not less than 12 times of cable outer diameter for cables with armor or copper wire screen structure.